Demo Setpoints

On Setpoint (ft.): 3.5
Off Setpoint (ft.): 1.5
Level @ Max Speed (ft.): 4.5
Level @ Min Speed (ft.): 2.0
% Max Speed: 100
% Min Speed: 50

As the wet well level rises, the L-Series increases the VFD speed in anticipatino of the start speed required for the lead pump (1R).

Once the wet well level reaches the "on" setpoint (3.5 ft.), the lead pump (1R) will begin to pump. The lag pump (2C) will begin to ramp up.

To Refresh the Animation, Simply Hold Down the Shift Key
and Hit Your Browser's Refresh/Reload Button.

   